期刊:IEEE TRANSACTIONS ON POWER SYSTEMS ISSN:0885-8950 , 年:2018 . 卷:33 . 期:4 页码:4189-4196
语种:
English
原文链接:http://dx.doi.org/10.1109/TPWRS.2017.2776968
-
- 摘要
-
Modern power system suffers voltage instability more frequently due to the increasing load. Sensitivity analysis based preventive control is widely recognized as an effective method for preventing voltage instability. However, the well-known load margin based sensitivity methods are not suitable for real-time application since they must solve the left eigenvector of zero eigenvalue of the Jacobi matrix at the critical point and require the system-wide information. Therefore, this paper proposes a fast sensitivity-based method for selecting the most effective preventive controls. The sensitivity analysis uses a local voltage stability index, i.e., load impedance modulus margin, which is derived from the local measurements (nodal voltage and current), and the sensitivity ranking can be obtained more accurately and faster than traditional methods based on load margin. Such computational advantages make it suitable for online application. The effectiveness of the proposed method is successfully validated by both small and large-scale power systems.
-
关键词
Voltage stability; preventive control; sensitivity analysis; load impedance module margin
- 作者信息
-
通讯作者:
Li, SH , Xiangtan Univ, Coll Informat Engn, Xiangtan 411105, Peoples R China.
作者机构:
[1]
[
Li, Shuaihu ]
Xiangtan Univ, Coll Informat Engn, Xiangtan 411105, Peoples R China.
[2]
[
Tan, Yi; Li, Canbing; Cao, Yijia ]
Hunan Univ, Coll Elect & Informat Engn, Changsha 410082, Hunan, Peoples R China.
[3]
[
Jiang, Lin ]
Univ Liverpool, Sch Elect Engn Elect & Comp Sci, Fac Sci & Engn, Liverpool L69 3GJ, Merseyside, England.
作者邮箱:
lishuaihu2010@126.com
yibirth-day@126.com
licanbing@qq.com
yjcao@hnu.edu.cn
L.Jiang@liverpool.ac.uk